全國谘詢熱線
NY-700B饋線弧光保護裝置
在我國,中、低(di)壓(ya)母(mu)線(xian)短(duan)路(lu)故(gu)障(zhang)中(zhong),重(zhong)點(dian)設(she)備(bei)和(he)人(ren)員(yuan)傷(shang)害(hai)主(zhu)要(yao)由(you)電(dian)弧(hu)光(guang)引(yin)起(qi),然(ran)而(er),我(wo)國(guo)的(de)大(da)多(duo)數(shu)中(zhong)低(di)壓(ya)母(mu)線(xian)沒(mei)有(you)設(she)置(zhi)快(kuai)速(su)母(mu)線(xian)保(bao)護(hu),而(er)隻(zhi)是(shi)采(cai)用(yong)了(le)簡(jian)單(dan)的(de)消(xiao)弧(hu)裝(zhuang)置(zhi)和(he)變(bian)壓(ya)器(qi)後(hou)備(bei)保(bao)護(hu)。這(zhe)些(xie)保(bao)護(hu)智(zhi)能(neng)化(hua)較(jiao)低(di),動(dong)作(zuo)速(su)度(du)慢(man),往(wang)往(wang)會(hui)延(yan)長(chang)故(gu)障(zhang)切(qie)除(chu)時(shi)間(jian),從(cong)而(er)進(jin)一(yi)步(bu)擴(kuo)大(da)設(she)備(bei)損(sun)壞(huai)程(cheng)度(du),甚(shen)至(zhi)會(hui)引(yin)起(qi)“火燒連營”的惡性事故,衝擊變壓器一次運行,影響整個電網的安全運行。
NY-700B饋(kui)線(xian)弧(hu)光(guang)保(bao)護(hu)係(xi)統(tong)是(shi)我(wo)公(gong)司(si)根(gen)據(ju)國(guo)內(nei)實(shi)際(ji)情(qing)況(kuang),吸(xi)收(shou)國(guo)外(wai)電(dian)弧(hu)光(guang)保(bao)護(hu)的(de)特(te)點(dian),結(jie)合(he)行(xing)業(ye)檢(jian)測(ce)及(ji)保(bao)護(hu)配(pei)置(zhi)相(xiang)關(guan)規(gui)程(cheng),自(zi)主(zhu)研(yan)發(fa)出(chu)具(ju)有(you)獨(du)特(te)創(chuang)新(xin)技(ji)術(shu)、具有廣泛實用性、高可靠性的新型電弧光保護係統。采用弧光檢測和過電流檢測雙判據原理,具有保護動作速度快、可靠性高等特點。
主要應用於電力變電站火、電廠電氣段開關櫃、風電場及光伏站開關櫃、箱式變電站、廠礦企業改造及新建項目、水利工程、醫院及學校等大型市政工程項目
電弧光保護係統作用
1)減少或降低電弧光對於人體的傷害;
2)減少或降低電弧光短路故障對於設備的損害;
3)避免變壓器因近距離母線故障造成動穩定破壞,延長變壓器的使用壽命;
4)縮短電弧光故障切除時間,避免波及站內直流係統造成重大損失;
5)減少因電弧光故障造成設備停運的時間,更快地恢複供電;
技術參數
3路饋線弧光保護裝置
序號 | 主要參數 | 功能 | 應用 |
1 | 工作電源 | 電源 | AC/DC85~265V(AC工頻:50Hz) 可定製DC48V,DC24V |
功耗 | 正常運行≤8W;裝置動作≤10W | ||
2 | 電流輸入 | 額定值In | 5A/1A |
測量範圍 | 保護電流:0~20In | ||
功耗 | 不大於0.5VA | ||
3 | 電參量誤差 | 保護電流 | 不大於4% |
保護頻率 | 0.1Hz | ||
4 | 弧光信號輸入 | 通道數 | 3路 |
傳感器類型 | 光纖型 | ||
檢測光類型 | 可見光/紫外光可選 | ||
5 | 動作時間誤差 | 純弧光保護 | ≤10ms |
雙判據保護 | ≤20ms | ||
6 | 繼電器輸出 | 通道數 | 4路(選配6路) |
工作電壓 | AC250V/8A | ||
輸入方式 | 無源接點 | ||
隔離方式 | 光電隔離,隔離電壓2500V | ||
7 | 485通訊 | 通訊接口 | RS485默認1路、可選配最大3路 |
隔離類型 | 光電隔離,帶防雷保護 | ||
波特率 | 9600bps | ||
通訊規約 | Modbus |